Omron

Omron S8FS-G60015C Power supply 600W, 100-240 VAC input, 15VDC, 40A output

Availability: Out of stock


0 / Piece | (Inc GST)
0.0  (+18.0% GST extra)
1 Piece/Pieces
(Min.Order)

Quantity
Quantity Price
1 - 10000 0

Omron S8FS-G60015C Power Supply With Cover/Direct Mounting,Covered type,100 to 240 VAC, Power rating 600W, Output: 15VDC, 40A Terminal block (Screw terminal), Harmonic current emissions,Omron Smps,Industrial use for Switch Mode Power Supply, Omron Industrial Smps,

Power rating

Item                                                     Output voltage

600 W

12 V

15 V

24 V

48 V

 

Efficiency *

100 VAC input

84% typ.

84% typ.

85% typ.

88% typ.

200 VAC input

88% typ.

88% typ.

89% typ.

92% typ.

230 VAC input

88% typ.

88% typ.

90% typ.

92% typ.

 

 

 

 

Input

Voltage range *

Single phase, 85 to 264 VAC, 120 to 350 VDC

Frequency *

50 /60 Hz(47 to 63 Hz)

Current *

100 VAC input

7.7 A typ.

200 VAC input

3.8 A typ.

Power factor

0.9 min.

Leakage current *

100 VAC input

0.5 mA max.

200 VAC input

1 mA max.

Inrush current *

(for a cold start at 25°C)

100 VAC input

14 A typ.

200 VAC input

28 A typ.

 

 

 

 

 

 

 

Output

Rated Output Current

50 A

40 A

27 A

13 A

Voltage adjustment range *

-10% to 15% (with V.ADJ)

Ripple & Noise voltage *

100 to 240 VAC input

170 mVp-p max.

170 mVp-p max.

280 mVp-p max.

340 mVp-p max.

Input variation influence *

0.5% max.

Load variation influence *

1.0% max.

Temperature variation influence

100 to 240 VAC input

0.05%/°C max.

Startup time *

100 VAC input

1,000 ms max.

200 VAC input

1,000 ms max.

 

 

Hold time *

 

100 VAC input

 

30 ms typ.

 

25 ms typ.

30 ms typ.

40 ms typ. (Extended hold time type)

 

30 ms typ.

 

200 VAC input

 

30 ms typ.

 

25 ms typ.

30 ms typ.

40 ms typ. (Extended hold time type)

 

30 ms typ.

 

 

 

Additional functions

Overload protection

Yes, automatic reset

Overvoltage protection *

Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again)

Overheat protection

Yes, power shut off (shut off the input voltage and turn on the input again)

Series operation

Yes (For up to two Power Supplies, external diodes are required.)

Parallel operation

Yes (up to five Power Supplies, S8FS-G60024 (models with parallel operation option) only).

Remote sensing

No

Remote control

Yes (Only Remote control)

Output indicator

Yes (LED: Green)

 

 

 

Insulation

 

 

Withstand voltage

3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA

2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA

1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA

Only Remote control

500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA

Insulation resistance

100 MÙ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC

 

 

Environment

Ambient operating temperature

-20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing)

Storage temperature

-25 to 75°C (with no condensation or icing)

Ambient operating humidity

90% max. (Storage humidity: 90% max.)

Vibration resistance

10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions

Shock resistance

150 m/s2, 3 times each in ±X, ±Y, ±Z directions

Reliability

MTBF

135,000 hrs min.

Life expectancy *

10 years min.

 

 

Construction

Dimensions (W×H×D)

Refer to Dimensions on page 26.

Weight

1,050 g

Cooling fan

Yes

Degree of protection

---

 

 

 

 

 

 

 

Standards

Harmonic current emissions

Conforms to EN 61000-3-2

EMI *

Conducted Emissions

Conforms to EN 61204-3 Class B, EN 55011 Class B

Radiated Emissions

Conforms to EN 61204-3 Class B, EN 55011 Class B

EMS

Conforms to EN 61204-3 high severity levels

 

 

 

Safety Standards

UL 508 (Listing, excluding models with remote control option) UL 508 (Recognition, models with remote control option)

UL 60950-1, UL 62368-1 (Recognition, OVCII [£ 3,000 m], Pol2)

CSA C22.2 No.107.1 (excluding models with remote control option)

CSA C22.2 No.60950-1, No.62368-1 (excluding models with remote control option) EN 50178 (OVCIII [£ 2,000 m], OVCII [> 2,000 m and £ 3,000 m], Pol2)

EN/IEC 60950-1, EN/IEC 62368-1 (OVCII [£ 3,000 m], Pol2)

Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1)

Marine Standards

No

SEMI

Conforms to F47-0706 (200 VAC input)

Related Products